Data point reference

All IDs are 16-bit. The high byte groups them roughly by function. Values in brackets are example readings from a running unit. This assignment applies to a P 2H-L and may differ on other configurations.

Control data points (writable)

Identified unambiguously by deliberate operation at the panel — changing the respective quantity at the panel changes exactly this data point:

DP Type Meaning Values
0x00e1 int16 Fan stage 0=off, 1, 2, 3, 4
0x020a int16 Operating mode 0=off, 1=Eco summer, 2=Eco winter, 3=Comfort, 4=Stove
0x0227 float32 Room setpoint 15–25 °C (panel rotary control)
0x0226 float32 Actual room temperature (panel sensor, can be fed in) —

Write frames:

Fan stage:      11 80 00 e1 00 00 00 04 <NN> 00 <crc16>   # NN = 01/02/03/04
Operating mode: 11 80 00 0a 02 00 00 04 <NN> 00 <crc16>
Room setpoint:  11 80 00 27 02 00 00 08 <float32 LE> <crc16>

Operating mode encoding

The encoding was determined directly on the bus: off=0, Eco summer=1, Eco winter=2, Comfort=3, Stove=4. It differs from the assignment sometimes passed around, which is derived from the related WR3223 range.

Temperature sensors

Ten physical channels. The names correspond to the T numbers from the panel's "Current readings" menu and were assigned by comparing simultaneous bus values against the panel display.

DP Sensor
0x0194 T1 supply air
0x0231 T3 fresh air
0x0230 T4 exhaust air
0x0190 T5 before evaporator
0x0191 T6 evaporator
0x022e T7 extract air
0x0192 T8 after preheater
0x022d T10 condenser
0x0193 T12 before condenser
0x0195 T13 compressor

Separating the supply-air pair 0x0194/0x022d

Both data points sit in the supply air path and read identically while the heat pump is off (constant idle offset of about 0.6 K). The assignment was determined during a controlled heat pump run (which can be triggered in summer too: Comfort mode, setpoint 5–6 K above room temperature; the compressor started in under two minutes here). On compressor start 0x022d rises earlier and far more steeply than 0x0194 (the sensor at the heat source leads), and after shutdown it holds residual heat longer once corrected for the idle offset. Both observations identify 0x022d as T10 condenser and 0x0194 accordingly as T1 supply air. Reference values from the run: T13 compressor 21 → 74 °C, T4 exhaust air 22 → 6 °C, T6 evaporator 24 → 7 °C, supply-air pair 21 → 49 °C.

Fans & speeds

DP Meaning
0x00c9 Actual speed, 2× float32 [supply, extract]
0x00d7 Target speed, 2× float32 [supply, extract]

Status data points

DP Meaning
0x0160 Summer bypass status: 0 = closed (heat recovery active), 1 = bypass active
0x00ed Filter remaining runtime in days (u32)
0x0130 Fault text (plain text)

Determining the bypass status

In an overnight long-term measurement 0x0160 was the only data point to change from 0 to 1 at exactly the moment when the fresh air temperature fell below the room temperature in the evening. From that moment the supply air temperature measurably detached from the extract air temperature and approached the fresh air — the damper movement is thereby evidenced against an independent quantity. The intermediate position of the supply air (between full heat recovery and full bypass) fits a controlled summer bypass. At the same moment 0x01f6 changed from 0x40 to 0x20 (status word candidate, meaning open).

Filter remaining runtime

At the time of measurement 0x00ed matched the panel's filter remaining runtime display exactly and was the only data point carrying that value in the entire address space. The daily decrement is confirmed; the only open question is the moment at which it happens (not midnight).

Counters and further data points read

DP Meaning
0x02df Operating hour counter array (u32 list, 9 slots in use, incremented hourly); individual values also readable as 0x02d0–0x02d9
0x0066 Array of 12 flags (u32) — presumably switched outputs; assignment open, the bypass status does not report here but in 0x0160
0x0064 Raw analogue values of the sensor channels (float32, mV; open channels sit at the 3.3 V reference)
0x03e8 Status / log text of the controller (e.g. "Writing parameters to NVRAM backup")
0x032e Operating time since start (seconds)
0x00d2 / 0x00d3 Fan stage → percentage characteristic curves
0x0233–0x023e Parameter block (winter / heat pump), writable only at the top access level

Observed constraints when writing

The following points are observations from the investigation, not instructions. They describe the behaviour of the bus that a writing implementation has to take into account:

  • A complete frame including the checksum is required; the checksum is described on the protocol page.
  • Cyclic repetition: the STM32 master retransmits the panel state about every 5 seconds. A single set frame is overwritten again by this; holding a state permanently requires repetition at a shorter interval (≈ 1.5 s proved effective in this investigation).
  • Independent verification of effect: the effect of a set frame can be observed on a quantity independent of it, for example the actual speed 0x00c9.
  • Fail-safe behaviour: if the master drops out, the unit keeps ventilating in a fallback state; it does not come to a standstill.